goodman furnace goes out when blower kicks on

goodman furnace goes out when blower kicks on

Posted On: March 2, 2023
As title states: furnace lights properly but as soon as the blower kicks on, the furnace turns off. Getting 3 flashes. (Pressure switch open). checked pressure switch no problem. Checks the rollout not tripped. However, I think I've diagnosed the problem but could use some insight. I took the panel off and it seemed to run better. My thought is better airflow. What I believe corroborates my story is I checked the exhaust outside and it goes back into the intake (very bad I know.). I am not the installer. I'll be moving the exhaust tomorrow so i...[More]





goodman furnace goes out when blower kicks on

goodman furnace goes out when blower kicks on

Posted On: March 2, 2023
As title states: furnace lights properly but as soon as the blower kicks on, the furnace turns off. Getting 3 flashes. (Pressure switch open). checked pressure switch no problem. Checks the rollout not tripped. However, I think I've diagnosed the problem but could use some insight. I took the panel off and it seemed to run better. My thought is better airflow. What I believe corroborates my story is I checked the exhaust outside and it goes back into the intake (very bad I know.). I am not the installer. I'll be moving the exhaust tomorrow so i...[More]



6 branch ducts within 4 of end of main duct

6 branch ducts within 4 of end of main duct

Posted On: March 1, 2023
Question from user gaislander at hvacadvice at reddit.com. Answer: This is right after my master bedroom, which is always hotter than the rest of the house with AC, and colder with heat. Four go to the master bathroom and two to the living room on the other side of the wall (facing left). New home. They have come out several times and last time came out and updated the two master bedroom branch ducts (the two before this picture) from 6 to 7 which helped a bit, but not fully. This is too many branches and too close to the end right? Will moving...[More]





6 branch ducts within 4 of end of main duct

6 branch ducts within 4 of end of main duct

Posted On: March 1, 2023
Question from user gaislander at hvacadvice at reddit.com. Answer: This is right after my master bedroom, which is always hotter than the rest of the house with AC, and colder with heat. Four go to the master bathroom and two to the living room on the other side of the wall (facing left). New home. They have come out several times and last time came out and updated the two master bedroom branch ducts (the two before this picture) from 6 to 7 which helped a bit, but not fully. This is too many branches and too close to the end right? Will moving...[More]



furnace went out is this a bad quote for a furnace and a c

furnace went out is this a bad quote for a furnace and a c

Posted On: February 28, 2023
Question from user tatanka_truck at hvacadvice at reddit.com. Answer: You dont need a special air-cleaner unless you have allergies or something and even if you do, it wont do much without running the fan all the time. The icomfort is expensive and for a 2-stage furnace with single stage a � c, a 2-stage generic thermostat will do fine at a lower cost � provided you have enough wires in the wall. the icomfort communicating stat is more beneficial on the more complex systems � like modulating furnace and variable capacity inverter a � c ...[More]





furnace went out is this a bad quote for a furnace and a c

furnace went out is this a bad quote for a furnace and a c

Posted On: February 28, 2023
Question from user tatanka_truck at hvacadvice at reddit.com. Answer: You dont need a special air-cleaner unless you have allergies or something and even if you do, it wont do much without running the fan all the time. The icomfort is expensive and for a 2-stage furnace with single stage a � c, a 2-stage generic thermostat will do fine at a lower cost � provided you have enough wires in the wall. the icomfort communicating stat is more beneficial on the more complex systems � like modulating furnace and variable capacity inverter a � c ...[More]



5 reasons your furnace won’t turn on

5 reasons your furnace won’t turn on

Posted On: February 26, 2023
It’s one thing to pull your covers up and enjoy the brisk weather, but it’s quite another issue to deal with a failing heating system. If you are unsure why your home’s furnace won’t kick on, then it may be time to troubleshoot how to your furnace repair yourself with these steps. Over the years, KDM has done lots of troubleshooting, and we put this list of steps together to help you understand why your furnace won’t turn on. Check Your Circuit Breakers The most common issue that can cause furnace problems is if the circuit breaker po...[More]





5 reasons your furnace won’t turn on

5 reasons your furnace won’t turn on

Posted On: February 26, 2023
It’s one thing to pull your covers up and enjoy the brisk weather, but it’s quite another issue to deal with a failing heating system. If you are unsure why your home’s furnace won’t kick on, then it may be time to troubleshoot how to your furnace repair yourself with these steps. Over the years, KDM has done lots of troubleshooting, and we put this list of steps together to help you understand why your furnace won’t turn on. Check Your Circuit Breakers The most common issue that can cause furnace problems is if the circuit breaker po...[More]



furnace burner not staying on after power outage

furnace burner not staying on after power outage

Posted On: February 25, 2023
Question from user PoliticalChess4 at hvacadvice at reddit.com. Answer: the small hose that travels from the draft inducer to the top of the drain trap should not be looped like that, and needs to be cut shorter. a little bit of water stuck in that tube will cause a e09 fault. also the furnace drain should be vented to help prevent this as well. Answer from user Supriselobotomy at hvacadvice at reddit.com. furnace burner not staying on after power outage The post furnace burner not staying on after power outage appeared first on KDM Gas. Re Pos...[More]





furnace burner not staying on after power outage

furnace burner not staying on after power outage

Posted On: February 25, 2023
Question from user PoliticalChess4 at hvacadvice at reddit.com. Answer: the small hose that travels from the draft inducer to the top of the drain trap should not be looped like that, and needs to be cut shorter. a little bit of water stuck in that tube will cause a e09 fault. also the furnace drain should be vented to help prevent this as well. Answer from user Supriselobotomy at hvacadvice at reddit.com. furnace burner not staying on after power outage The post furnace burner not staying on after power outage appeared first on KDM Gas. Re Pos...[More]



natural gas furnace help

natural gas furnace help

Posted On: February 25, 2023
So full disclosure, I am an HVAC service tech. 6 years experience but always learning. My mom's trane natural gas furnace goes out. Getting error code that says out on retries. System cycles through its normal startup procedure, and gets to where the ignitor glows, control board clicks to send power to gas valve. Nothing happens. I disconnect the 2 leads and when disconnected, I have 27 volts across when the control board is energizing the gas valve. Ok, bad gas valve. I order new gas valve and replace. Same thing happens. I think, ok maybe bad...[More]





natural gas furnace help

natural gas furnace help

Posted On: February 25, 2023
So full disclosure, I am an HVAC service tech. 6 years experience but always learning. My mom's trane natural gas furnace goes out. Getting error code that says out on retries. System cycles through its normal startup procedure, and gets to where the ignitor glows, control board clicks to send power to gas valve. Nothing happens. I disconnect the 2 leads and when disconnected, I have 27 volts across when the control board is energizing the gas valve. Ok, bad gas valve. I order new gas valve and replace. Same thing happens. I think, ok maybe bad...[More]



this is connected to my ac unit is this normal

this is connected to my ac unit is this normal

Posted On: February 23, 2023
Saw this today, this is connected to my AC unit,  Is this normal? I haven’t used the AC since summer, what happened? Question from user nyjetsny1 at hvacadvice at reddit.com. Answer: What do you mean what happened? Why do you think something happened? Answer from user HydrogenxPi at hvacadvice at reddit.com. this is connected to my ac unit is this normal The post this is connected to my ac unit is this normal appeared first on KDM Gas. Re Posted From: this is connected to my ac unit is this normalKDM Gas...[More]





this is connected to my ac unit is this normal

this is connected to my ac unit is this normal

Posted On: February 23, 2023
Saw this today, this is connected to my AC unit,  Is this normal? I haven’t used the AC since summer, what happened? Question from user nyjetsny1 at hvacadvice at reddit.com. Answer: What do you mean what happened? Why do you think something happened? Answer from user HydrogenxPi at hvacadvice at reddit.com. this is connected to my ac unit is this normal The post this is connected to my ac unit is this normal appeared first on KDM Gas. Re Posted From: this is connected to my ac unit is this normalKDM Gas...[More]



i am not crazy right

i am not crazy right

Posted On: February 20, 2023
i have this “extra” hole cut right out the panel, and one “extra” hole at the top next to the power. Both are pulling air in, i think the guy doing the install has no idea what he was doing. My house is full of dust more than it should be , im guessing these holes are pulling in all the garage air into my system and into my house. Am i crazy but that is not how these systems work the plans don't show ” extra” holes for pulling “extra” unfiltered air in system is carrier FSM2X2400A in vertical position with up flow. Question from...[More]





i am not crazy right

i am not crazy right

Posted On: February 20, 2023
i have this “extra” hole cut right out the panel, and one “extra” hole at the top next to the power. Both are pulling air in, i think the guy doing the install has no idea what he was doing. My house is full of dust more than it should be , im guessing these holes are pulling in all the garage air into my system and into my house. Am i crazy but that is not how these systems work the plans don't show ” extra” holes for pulling “extra” unfiltered air in system is carrier FSM2X2400A in vertical position with up flow. Question from...[More]



is this a reasonable estimate for a new a c and furnace

is this a reasonable estimate for a new a c and furnace

Posted On: February 19, 2023
Question from user knorrt23 at hvacadvice at reddit.com. Answer: I'm not a tech. But. Based on installing 2 units at my house and my son installing 1 in 2022. Seems reasonable. Get a couple more quotes. Answer from user Jhc3964 at hvacadvice at reddit.com. is this a reasonable estimate for a new a c and furnace The post is this a reasonable estimate for a new a c and furnace appeared first on KDM Gas. Re Posted From: is this a reasonable estimate for a new a c and furnaceKDM Gas...[More]





is this a reasonable estimate for a new a c and furnace

is this a reasonable estimate for a new a c and furnace

Posted On: February 19, 2023
Question from user knorrt23 at hvacadvice at reddit.com. Answer: I'm not a tech. But. Based on installing 2 units at my house and my son installing 1 in 2022. Seems reasonable. Get a couple more quotes. Answer from user Jhc3964 at hvacadvice at reddit.com. is this a reasonable estimate for a new a c and furnace The post is this a reasonable estimate for a new a c and furnace appeared first on KDM Gas. Re Posted From: is this a reasonable estimate for a new a c and furnaceKDM Gas...[More]



coldest air conditioner

coldest air conditioner

Posted On: February 18, 2023
I have a hard time sleeping if it doesn't feel like a freezer in my room. It's 26°f outside rn and I have my window open. I've found that my AC unit, only barely being able to chill the room to 61°f, doesn't do the trick. It might just be too small for the room but 61° still isn't cold enough for me. Is there any way to cool a room to maybe 40° without actually having to sleep in a refrigerator? Thanks. Question from user Bswih at hvacadvice at reddit.com. Answer: If its 26 F outside, you're better off just putting in a window fan a...[More]





coldest air conditioner

coldest air conditioner

Posted On: February 18, 2023
I have a hard time sleeping if it doesn't feel like a freezer in my room. It's 26°f outside rn and I have my window open. I've found that my AC unit, only barely being able to chill the room to 61°f, doesn't do the trick. It might just be too small for the room but 61° still isn't cold enough for me. Is there any way to cool a room to maybe 40° without actually having to sleep in a refrigerator? Thanks. Question from user Bswih at hvacadvice at reddit.com. Answer: If its 26 F outside, you're better off just putting in a window fan a...[More]



TOP